VFD Cables

     


 VFD Cables


VFD Cable with EMC Screening

Application

EMC VFD cable has been specially designed for Variable Frequency Drive Motors and installations where it is

necessary to limit the effects of electromagnetic interference (EMI).

Construction


Conductor

Electrolytic copper,class 5 (flexible),based on EN/IEC 60228

Grouding Conductor

The grounding conductor is divided into three conductors; the equivalent cross section is approximately 50% of the section of the phase conductor.

Insulation

Cross-linked polyethylene (XLPE) 4G grey + brown + black + Green/yellow (up to 4 mm2) 3x + 3G grey + brown + black + Green/yellow (3 x) (from 6 mm2 onwards)

Screen

Aluminium-polyester tape screen, helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the the electromagnetic interference. The screen has a cover of 100% and its total section is approximately 10% of one of the conductors.

Outer Jacket

Polyolefin LSZH outer sheath with ripcord to allows for ease of stripping of the outer jacket.

Technical Information

Electrical performance

LOW VOLTAGE 0.6/1 KV

Standrd

IEC 60502-1 / IEC 60092-353

Thermal performance

Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).

Fire performance

 

Flame non-propagation

based on UNE-EN 60332-1 and IEC 60332-1.

Fire non-propagation

based on UNE-EN 60332-3 and IEC 60332-3.

LSZH(Low Smoke Zero Halogen)

based on UNE-EN 60754-1 and IEC 60754-1.

Low smoke emission

based in UNE-EN 61034 and IEC 61034:Light transmittance>60%

Low corrosive gases emission

based on UNE-EN 60754-2 and IEC 60754-2.

Mechanical performance

 

Minimum bending radius:

x10 cable diameter.

Impact resistance:

AG2 Medium severity.

Chemical performance

Chemical & Oil resistance: Good.

Water performance

Water resistance: AD5 Jets.

Installation conditions

Open Air. Buried. In conduit.

Applications

Industrial use. Variable Frequency Drive (VFD)

Cable Parameter


No.of cores x cross section

Outer-Ø ca.mm

Copper weight

Cable weight approx.

AWG

n x mm2

± 10%

kg/km

kg/km

 

4G1.5

10.6

95

230

16

7G1.5

12.9

151

362

16

4G2.5

12.3

150

300

14

7G2.5

14

265

450

14

4G4

14.5

235

485

12

4G6

16.2

320

633

10

4G10

19.2

533

863

8

4G16

22

789

1291

6

4G25

27

1236

1862

4

4G35

30

1662

2611

2

4G50

35

2345

2955

1

4G70

40.8

3196

3953

2/0

4G95

45.8

4316

5304

3/0

4G120

49.7

5435

6604

4/0

4G150

57

6394

7043

250 MCM

4G185

61.1

7639

8384

350 MCM

4G240

67

10013

11010

450 MCM

4G300

71.5

12570

13800

550 MCM

3x1.5+3G0.25

10.2

86

140

16/24

3x2.5+3G0.5

11.4

144

220

14/20

3x4+3G0.75

13

224

323

12/19

3x6+3G1

15

298

420

10/18

3x10+3G1.5

18.4

491

615

8/16

3x16+3G2.5

21.6

723

819

6/14

3x25+3G4

25.3

1000

1200

4/12

3x35+3G6

27.8

1350

1600

2/10

3x50+3G10

32.6

2208

2399

1/8

3x70+3G10

39

2871

3080

2/0/8

3x95+3G16

44.3

3953

4180

3/0/6

3x120+3G16

46.3

4300

4700

4/0/6

3x150+3G25

53.5

5450

5900

250 MCM/4

3x185+3G35

59.5

6969

7189

350 MCM/2

3x240+3G42.5

65.2

8850

9540

450 MCM/1

3x300+3G50

69.5

10700

11560

550 MCM/1